Specifications
Input (DC) | |
Recommended max PV input power | 30000 W |
Max PV input voltage | 1100 V |
Start-up input voltage | 250 V |
Rated input voltage | 580 V |
MPP voltage range | 160 V – 1000 V |
No of independent MPP inputs | 2 |
No of PV strings per MPP | 2 |
Max input current per MPP tracker | 27 A |
Max short-circuit current per MPP tracker | 338 A |
Output (AC) | |
Rated AC output power | 20000 W |
Max AC output apparent power | 22000 VA |
Rated AC voltage(range) | 220/380 V, 230/400 V (340-440 V) |
Max output current | 319 A |
AC grid frequency | 50 Hz / 60 H |
AC grid frequency range | 45 – 55 Hz / 55 – 65 Hz |
Harmonic (THD) | < 3 % (at rated power) |
Adjustable power factor | 08 leading – 08 lagging |
AC grid connection type | 3 W + N + PE |
Efficiency | |
Max efficiency | 9875% |
European efficiency | 986% |
MPPT efficiency | 999% |
Protection devices | |
Grid monitoring | yes |
DC reverse polarity protection | yes |
AC short-circuit protection | yes |
Insulation resistance monitoring | yes |
Surge Protection | DC Type II / AC Type II |
Ground fault monitoring | yes |
DC switch | yes |
String monitoring | yes |
Arc fault circuit interrupter (AFCI) | optional |
Anti-islanding protection | yes |
Residual-current monitoring unit | yes |
General Data | |
Dimensions(W*H*D) | 525*395*222 m |
Weight | 23 kg |
Topology | Transformerless |
Degree of protection | IP65 |
Night power consumption | < 1 W |
Operating ambient temperature range | -25 °C to +60 °C |
Allowable relative humidity range (non-condensing) | 0% – 100% |
Cooling method | Smart air cooling |
Max operating altitude | 4000 m |
Display | OLED + LED / WiFi + app |
Interfaces | RS-485 / USB |
Optional interfaces | Wi-Fi / GPRS / RF / LAN |
DC connection | H4 / MC4 (optional) |
AC connection | Cable gland + OT terminal |
Certification | CE, VDE0126, Greece, EN50549, C10/C11, UTE C 15-712, IEC62116, IEC61727, IEC 60068, IEC 61683, CEI0-21, N4105, TOR Erzeuger G98/G99, G100, UNE217001, UNE206007, PO122, KSC8565 |
Warranty:
The warranty of the voltage converter (inverter) is valid from the day when we (the seller) is provided with the serial number of the inverter, the purchase invoice, a certified electrician’s certificate about the installed:
1) Lightning protection and overvoltage limiter (on the input side)
2) Lightning protection (between solar panels and inverter)
3) DC voltage switch between panels and inverter
4) Dedicate grounding for solar panels separated from grounding of the house
The 5-year (60-month) manufacturer’s warranty begins from the day of purchase, but comes into effect only after submission of these documents
Note: Lightning strike is not a valid warranty claim, it is classified as insurance claim
Reviews
There are no reviews yet.